Five procedures. Procedure 0 is not negotiable.
Procedure 0 — Safe the squib (R1)
Before any work on an extinguishing circuit.
- De-energize the aircraft electrical system as the manual requires.
- Disconnect the squib connector at the bottle.
- Cap or short the connector per the manual, so no induced current can reach it.
- Never apply an ohmmeter or any test set to a squib circuit unless the manual specifies a method and an instrument for it (GEN-K Concepts §4).
Check — say out loud that the squib is disconnected, and point at the capped connector.
Failure — a discharged bottle. At best expensive and messy; at worst it happens in your face (AF-M Concepts §1).
Procedure 1 — Inspect a fire detection system (S9, S12, S3, S4)
- Trace the loop routing — security, support at the specified intervals, clearance from structure and from moving parts.
- Inspect the sensing element for chafe, kinks, crushing and corrosion. Chafe is the commonest defect and it produces false warnings (AF-M Concepts §2).
- Inspect connectors and end fittings.
- Check thermal switches or thermocouples where fitted, and their security.
- Inspect smoke and CO detectors — cleanliness, sensor life, security.
Check — a false fire warning is a loop fault until proven otherwise. Inspect the loop before condemning the control unit.
Procedure 2 — Operational check of a detection system (S10, S13)
- Do the press-to-test first, and understand what it proved: the lamp and the warning circuit (AF-M Concepts §4).
- Then perform the system operational check by the manual's method, which exercises the detection function itself.
- Confirm the warning appears, and that it clears when the test condition is removed.
- Check any fault or short monitoring function.
- Record which check you performed — press-to-test and an operational check are different entries.
Check — write down which test you did. "Fire system checked" is ambiguous, and ambiguity here means a dead loop signed off as serviceable.
Procedure 3 — Inspect an extinguisher bottle (S8, S2, S11)
- Procedure 0.
- Check the hydrostatic test date against the manufacturer's interval. Out of date is unairworthy regardless of condition.
- Check the discharge cartridge date — cartridges have their own life limit.
- Read the pressure gauge and the ambient temperature, and compare against the pressure-temperature chart. Neither number means anything alone (AF-M Concepts §3).
- Inspect the bottle: corrosion, dents, mounting security, discharge line condition.
- Check blowout plugs — a missing thermal plug means the bottle discharged from overheat, a missing discharge indicator means it was fired.
Check — read the chart, not the gauge. A bottle low on a cold morning may be correctly charged.
Procedure 4 — Inspect a discharge circuit (S8, with R1)
- Procedure 0 — squib disconnected and capped.
- Inspect wiring to the bottle for security, chafe and connector condition.
- Check the discharge switch and its guard.
- Check continuity of the circuit only by the manual's specified method and instrument — never with an ordinary ohmmeter.
- Reconnect the squib last, after all other work is complete, and confirm the guard is in place.
Check — the squib goes back on last, and nothing is done to the circuit afterwards. If something else needs doing, disconnect it again.
The checks, collected
| Procedure | The check |
|---|---|
| Safe the squib | Say it aloud and point at the capped connector |
| Detection inspection | A false warning is a loop fault until proven otherwise |
| Operational check | Write down which test you actually performed |
| Bottle | Read the pressure-temperature chart, not the gauge |
| Discharge circuit | Squib reconnected last, and nothing after |